Product
+
  • undefined

QJ 25-J series gas relay

The QJ-25-J series gas relay is a protective device used in on-load tap changers of oil-immersed transformers. When a transformer internal fault causes gas generation from oil decomposition or oil surge, the relay contacts will operate, closing the specified control circuit and promptly issuing a signal or automatically tripping the transformer breaker.

Keywords:

Product Inquiry:

Product Description

Product Introduction

The QJ-25-J series gas relay is a protective device used in on-load tap changers of oil-immersed transformers. When the transformer's internal fault causes gas generation due to oil decomposition or oil surge, the relay contacts will operate, connecting the specified control circuit and promptly issuing a signal or automatically disconnecting the transformer switch. 
An operation signal memory device has been added. When the baffle plate operation leads to heavy gas operation, this device can maintain the heavy gas signal to distinguish it from the situation where the heavy gas operation signal is caused by problems in the secondary circuit of the relay. A reset device for the operation signal has also been designed to restore the operation signal to its original position after the fault is eliminated.

Model Description

 
Example: 0J4-25ATH-J indicates a gas relay with memory function, designed for the 4th time, with a pipe diameter of 25mm, equipped with a gas sampling box, and suitable for humid and tropical regions. 
Note: The letter "G" after the design serial number indicates an improved product.

Special Environments

"TH" - For humid and tropical regions

"TA" - For tropical dry regions

Unspecified general type

Conditions of Use

Operating Temperature: -45℃~100℃

Installation: The relay pipeline axis should be parallel to the transformer box cover. The end leading to the oil reservoir can be slightly higher, but the inclination of its axis to the horizontal plane should not exceed 4%.

Product Model

Model Accumulated Gas Volume (mL) Oil Speed Setting Range (m/s) Factory Set Oil Flow Rate (m/s) Wiring Diagram
QJ4-25-J 200-250 1.0±0.1 1.0±0.1
QJ4G-25-J / 1.0±0.1 1.0±0.1
QJ5-25-J 200-250 1.0±0.1 1.0±0.1
QJ6-25-J / 1.0±0.1 1.0±0.1
QJ7-25-J 200-250 1.0±0.1 1.0±0.1
QJ7G-25-J 200-250 1.0±0.1 1.0±0.1
QJ8-25-J 200-250 1.0±0.1 1.0±0.1

 

Contact Capacity

Power Supply Type Operating Voltage Operating Current Description
DC 220V 0.3A Time Constant 
S≤5×10-3 -3 S
AC Power Factor 
Cos φ≤0.6

 

Appearance and Installation Dimensions

 

D1 D2 D3 D4 D5 D6 H1 H2 L1 L2 L3
φ25 φ85 φ36 φ64 φ14 φ115 183.5 126 200 127.5 15